Airdac SNE Cable House Service Connecting Cable with or without Pilot Cores SANS 1507-6

Circular stranded hard drawn copper phase conductor, XLPE insulated with concentrically arranged identified neutral and bare earth conductors. Polyethylene sheathed 600/1000V service connection cable. Nylon ripcord laid under sheath. Manufactured to SANS 1507 -6.

Description

    Circular stranded hard-drawn copper phase conductor, XLPE insulated with concentrically arranged bare earth conductors.Polyethylene sheathed 600/1000 V house service connection cable. Nylon ripcord laid under sheath.

 

    Small overall diameter - concentric construction

    Lower mass - due to smaller diameter - no steel wire armour

    Increased safety - reliable earthing

    Improved reliability - UV stable sheath and core insulation

    Tamper and vandal proof - unauthorised access to phase conductor inhibited by concentric layer

    Easy strip with nylon ripcord


Applicable Standard
    SANS 1507-6

Dimension Characteristics Electrical Properties

Cable Size (mm²) 10 16
Phase Conductor Resistance (Ohm/km) DC @20°C 1.90 1.20
Earth Size (mm²) 7.5 10
Netural Size (mm²) 10 16
Phase Core Impedance (Z) (Ohm/km) 2.34 1.47
Current Rating *(A) 50 70
Pilot Core (No. X OD) Soild (mm) 2 x 1.13 2 x 1.13

*Note: - In air, with 30 °C ambient with maximum conductor temperature 90 °C


Mechanical Properties

Cable Size (mm²) 10 16
Phase Conductor (No. X OD) (mm) 7 x 1.35 7 x 1.67
Nominal Insulation Thickness (mm) 1.0 1.0
Netural Conductor (No. X OD) (mm) 7 x 1.33 7 x 1.76
Earth Conductor (No. X OD) (mm) 3 x 1.78 3 x 2.20
Nominal Sheath Thickness (mm) 1.6 1.6
Approximate Cable OD (mm) 12.8 14.5
Approximate Cable Mass (kg/km) 320 485

 