Cable 10mm2 PVC Concentric AA Cables Insulated

The cable shall be a service cable for continuous operation outdoors and tropical conditions.
The cable shall be suitable for laying in cable ducts and in air.
Permissible continuous loading operating temperature shall be 70℃.

Application

    The cable shall be a service cable for continuous operation outdoors and tropical conditions (temperature range of -1℃ to +40℃, humidity of up to 90% and saline conditions along the coast).

    The cable shall be suitable for laying in cable ducts and in air.

    Permissible continuous loading operating temperature shall be 70℃.

 

Applicable Standard
    IEC 60502-1

    KS 04-1022

 

Cable Construction Phase Conductor

    The phase conductor shall be circular stranded annealed aluminum conductors (class 2).The phase conductor shall have a left-hand direction of lay. The raw material used for aluminum conductors must have a minimum purity of 99.5%. In both cases the requirements of Standard IEC 60228 must be complied with.

Insulation
    The insulation of the phase conductor shall be black PVC (XLPE is optional). It shall be applied by an extrusion process and shall be spark tested.

Concentric Layer
    The neutral conductor shall be concentric and shall be manufactured from plain annealed aluminum wires. The concentric layer shall be applied with a right hand direction of lay.

Over sheath
    The over sheath shall be an extruded layer of black PVC compound.

 

 