0.6/1kV CU/XLPE/AWA/PVC Electric Power Cable IEC 60502-1

Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.

Description
    Electric cable with aluminum conductors, XLPE insulation, PVC bedding, galvanized steel wires armour (AWA) and PVC outer sheath

Application
    Multi-core PVC cable with steel wire armour (AWA). Power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.

Applicable Standard
    IEC 60228

    IEC 60502-1

Cable Construction
    Conductor: Compact stranded aluminum conductor, Cl.2 as per IEC 60228

    Insulation: XLPE(cross-linked polyethylene) rated at 90 OC

    Inner sheath: PVC

    Armored: Aluminum  Wire.

    Sheath: PVC or FR-PVC type ST2 to IEC 60502, black

 

Dimension Characteristics

Section Insulation Thickness Sheath Thickness Overall Diameter Cable Weight DC. Electrical Resistance at 20°C
No.xmm2 mm mm mm Cu Al Cu Al
kg/km Ω/km
1x10 0.7 1.8 13.7 277 215 1.83 3.08
1x16 0.7 1.8 14.7 352 252 1.15 1.91
1x25 0.9 1.8 16.4 454 304 0.727 1.20
1x35 0.9 1.8 17.0 562 352 0.524 0.868
1x50 1.0 1.8 19.4 774 485 0.387 0.641
1x70 1.1 1.8 21.1 1010 590 0.268 0.443
1x95 1.1 1.8 22.8 1275 700 0.193 0.320
1x120 1.2 1.8 25.2 1592 867 0.153 0.253
1x150 1.4 1.8 27.1 1929 1017 0.124 0.206
1x185 1.6 1.8 29.1 2289 1170 0.0991 0.164
1x240 1.7 1.9 31.8 2886 1421 0.0754 0.125
1x300 1.8 1.9 34.2 3475 1657 0.0601 0.100
1x400 2.0 2.1 38.7 4558 2200 0.0470 0.0778
1x500 2.2 2.2 42.3 5699 2652 0.0366 0.0605
1x630 2.4 2.3 46.4 7073 3141 0.0283 0.0469
1x800 2.6 2.5 52.6 9039 4025 0.0221 0.0367

 

 

 

  • Brand
    NPC CABLE