0.415kV 4x25mm2 NYY PVC (CU) LT UG Distribution Network Material

This power cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be expected.

Application
    Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.

Applicable Standard
    IEC 60502-1

Characteristics
    Voltage Rating Uo/U: 0.6/1 kV
    Temperature Rating:  Fixed: -15°C to + 70°C  Flexed: -15°C to + 50°C
    Minimum Bending Radius: Fixed: 12 x Overall Diameter (O.D.)


Cable Construction 
Conductor
    RE: Class 1 solid copper conductor
    RM: Class 2 stranded copper conductor


Insulation
    PVC (Polyvinyl Chloride)

Filler
    PVC (Polyvinyl Chloride)

Sheath
    PVC (Polyvinyl Chloride)


Dimension Characteristics

 

Section Insulation Thickness Sheath Thickness Overall Diameter Cable Weight DC. Electrical   Resistance at 20°C
No.xmm2 mm mm mm Cu Al Cu Al
kg/km Ω/km
4x0.5 0.8 1.8 10.6 123 - 36.0 -
4x0.75 0.8 1.8 11.1 140 - 24.9 -
4x1.5 0.8 1.8 12.1 185 147 12.1 18.1
4x2.5 0.8 1.8 13.0 236 174 7.41 12.1
4x4 1.0 1.8 15.2 338 238 4.61 7.41
4x6 1.0 1.8 16.4 435 283 3.08 4.61
4x10 1.0 1.8 19.6 645 392 1.83 3.08
4x16 1.0 1.8 22.0 909 507 1.15 1.91
4x25 1.2 1.8 26.1 1353 719 0.727 1.20
4x35 1.2 1.8 27.5 1720 854 0.524 0.868
4x50 1.4 1.9 27.7 2196 1023 0.387 0.641
4X70 1.4 2.1 31.8 3054 1357 0.268 0.443
4X95 1.6 2.2 41.2 4346 1989 0.193 0.320
4X120 1.6 2.4 45.2 5386 2412 0.153 0.253
4X150 1.8 2.5 50.0 6615 2946 0.124 0.206
4X185 2.0 2.7 55.2 8223 3632 0.0991 0.164
4X240 2.2 2.9 62.2 10686 4652 0.0754 0.125
4X300 2.4 3.1 68.9 13309 5739 0.0601 0.100
4x400 2.6 3.4 77.5 16916 7236 0.0470 0.0778
4x500 2.8 3.6 86.1 21477 9046 0.0366 0.0605

 

 