Instrumentation Cables—PVC Insulated,Individual &Overall Screened, Wire Armoured PVC Sheathed Cables(CU/PVC/IOSCR/SWA/PVC)
- Standard BS EN 50288-7, IEC 60502-1 (General)
Construction
Conductor
Insulation
Individual and Overall Screen
Armour
Inner and Outer Sheath
Technical Specifications
| Conductor Size | Max. Conductor DC Resistance at 20°C for Plain Copper |
Max. Conductor DC Resistance at 20°C for Tinned Copper |
||
| Solid, Class - 1 & Stranded, Class - 2 |
Flexible, Class-5 | Solid, Class - 1 & Stranded, Class - 2 |
Flexible, Class-5 | |
| [mm2] | [Ω/km] | [Ω/km] | [Ω/km] | [Ω/km] |
| 0.50 | 36.72 | 39.78 | 37.434 | 40.902 |
| 0.75 | 24.99 | 26.52 | 25.296 | 27.234 |
| 1.00 | 18.462 | 19.89 | 18.564 | 20.4 |
| 1.50 | 12.342 | 13.566 | 12.444 | 13.974 |
| 2.50 | 7.5582 | 8.1396 | 7.7112 | 8.3742 |
| Conductor Size | Insulation Thickness | |||
| 90V | 300V | 500V | 1000V | |
| [mm2] | [mm] | [mm] | [mm] | [mm] |
| 0.50 | 0.20 | 0.26 | 0.44 | 0.70 |
| 0.75 | 0.20 | 0.26 | 0.44 | 0.70 |
| 1.00 | 0.26 | 0.26 | 0.44 | 0.70 |
| 1.50 | 0.30 | 0.35 | 0.44 | 0.70 |
| 2.50 | - | - | 0.53 | 0.70 |
| Conductor Size | Mutual Capacitance | Max. Continuous Operating Temperature | Inductance to Resistance Ratio (L/R) |
||
| XLPE | PVC | XLPE or HR - PVC | PVC | ||
| [mm2] | [nF/km] | [nF/km] | [°C] | [°C] | [μH/Ω] |
| 0.50 | 150 | 250 | 90 | 70 | < 25 |
| 0.75 | 150 | 250 | 90 | 70 | < 25 |
| 1.00 | 150 | 250 | 90 | 70 | < 25 |
| 1.50 | 150 | 250 | 90 | 70 | < 40 |
| 2.50 | 150 | 250 | 90 | 70 | < 60 |
| Number of Pair | Cable OD | Cable Weight | Drum Length | ||||||||
| 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | ||
| [Nos] | [mm] | [mm] | [mm] | [mm] | [mm] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [m] |
| 2 | 14.0 | 14.5 | 15.5 | 16.5 | 19.0 | 315 | 345 | 375 | 435 | 550 | 1000 |
| 5 | 17.0 | 18.0 | 18.5 | 20.5 | 24.5 | 470 | 520 | 575 | 680 | 1000 | 1000 |
| 10 | 23.0 | 24.5 | 25.5 | 28.0 | 34.0 | 840 | 960 | 1065 | 1265 | 1840 | 1000 |
| 20 | 28.0 | 30.5 | 32.0 | 36.5 | 42.5 | 1270 | 1480 | 1650 | 2200 | 2930 | 1000 |
| 30 | 32.5 | 36.0 | 38.0 | 42.0 | 1690 | 2160 | 2430 | 2935 | 500 | ||
| Number of Triad | Cable OD | Cable Weight | Drum Length | ||||||||
| 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | ||
| [Nos] | [mm] | [mm] | [mm] | [mm] | [mm] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [m] |
| 2 | 15.0 | 16.0 | 17.0 | 18.0 | 21.5 | 360 | 415 | 455 | 510 | 760 | 1000 |
| 5 | 18.0 | 19.5 | 20.5 | 23.0 | 27.0 | 545 | 630 | 710 | 945 | 1240 | 1000 |
| 10 | 25.0 | 27.0 | 28.5 | 31.0 | 37.5 | 1000 | 1160 | 1315 | 1555 | 2300 | 1000 |
| 20 | 31.0 | 34.5 | 36.5 | 40.0 | 1550 | 2010 | 2300 | 2755 | 500 | ||
| 30 | 37.0 | 40.0 | 42.5 | 2280 | 2685 | 3065 | 500 | ||||
| Number of Quad | Cable OD | Cable Weight | Drum Length | ||||||||
| 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | 0.5mm² | 0.75mm² | 1.0mm² | 1.5mm² | 2.5mm² | ||
| [Nos] | [mm] | [mm] | [mm] | [mm] | [mm] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [kg/km] | [m] |
| 2 | 17.0 | 18.0 | 18.5 | 20.5 | 24.5 | 435 | 485 | 530 | 630 | 920 | 1000 |
| 5 | 20.5 | 23.0 | 24.0 | 26.5 | 30.5 | 665 | 880 | 975 | 1160 | 1530 | 1000 |
| 10 | 28.5 | 30.5 | 33.0 | 37.0 | 43.0 | 1220 | 1430 | 1630 | 2140 | 2885 | 1000 |
| 20 | 36.5 | 39.5 | 42.0 | 2105 | 2495 | 2845 | 500 | ||||
| 30 | 42.5 | 2795 | 500 | ||||||||
Note: Cable OD and Cable weight are subject to change based on the latest manufacturing practice.
Quality Control
Raw Material Test
Raw material testing for the Instrumentation Cables—PVC Insulated, Individual & Overall Screened, Wire Armoured PVC Sheathed Cables (CU/PVC/IOSCR/SWA/PVC) adheres to BS EN 50288-7. Step 1: Analyze copper purity via X-ray per IEC 60228. Step 2: Test PVC dielectric (20 kV/mm) with high-voltage setups. Step 3: Inspect screening foils/drain for conductivity/thickness. Step 4: Evaluate SWA wires for corrosion via salt spray. Step 5: Check sheath retardants with oxygen index tests. Step 6: Conduct tensile/elongation on insulation. Step 7: Immerse materials in chemicals for compatibility. Step 8: Trace batches with certifications. 15% sampling ensures dual-armoured quality.
Process inspection
Process inspection of the Instrumentation Cables—PVC Insulated, Individual & Overall Screened, Wire Armoured PVC Sheathed Cables (CU/PVC/IOSCR/SWA/PVC) complies with BS EN 50288-1. Step 1: Control stranding with dynamometers for consistency. Step 2: Monitor insulation uniformity via ultrasonics. Step 3: Verify pair lay and individual screens. Step 4: Apply overall screen; test with eddy currents. Step 5: Install armour; check tension/adhesion. Step 6: Run voltage continuity during assembly. Step 7: Inspect the sheath every 200 meters. Step 8: Log for audits. Ensures high-interference resistant armoured build per standards.
Finished Product
Finished testing for the Instrumentation Cables—PVC Insulated, Individual & Overall Screened, Wire Armoured PVC Sheathed Cables (CU/PVC/IOSCR/SWA/PVC) verifies BS EN 50288-7. Step 1: Apply 1 kV AC for breakdown. Step 2: Measure conductor DC resistance. Step 3: Test dual-screen EMI attenuation. Step 4: Perform armour crush/impact. Step 5: Check thermal stability at 70°C. Step 6: Assess water absorption on sheath/armour. Step 7: Evaluate capacitance/crosstalk. Step 8: Certify post-inspection. Batch testing confirms superior interference resistance.
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What are the advantages of power cables and overhead lines?(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people; (2) The maintenance workload is small and frequent inspections are not required; (3) No need to erect towers; (4) Help improve power factor.
-
Which aspects should be considered when choosing the cross section of a power cable?(1) The long-term allowable working current of the cable; (2) Thermal stability once short circuited; (3) The voltage drop on the line cannot exceed the allowable working range.
-
What are the measures for cable fire prevention?(1) Use flame-retardant cables; (2) Use fireproof cable tray; (3) Use fireproof paint; (4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.; (5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
-
What should be paid attention to during the transportation and handling of cables?(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat. (2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
-
What inspections should be carried out for the acceptance of cable lines?(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear; (2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements; (3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements; (4) Good grounding; (5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted; (6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.