x
400kVA Oil Immersed Transformer1
400kVA Oil Immersed Transformer2
400kVA Oil Immersed Transformer4
400kVA Oil Immersed Transformer1
400kVA Oil Immersed Transformer2
400kVA Oil Immersed Transformer4

400kVA Oil Immersed Transformer

The 400kVA Oil Immersed Transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is made of high-quality cold-rolled silicon steel sheet; the high-voltage winding is made of high-quality oxygen free copper wire and adopts a multi-layer cylindrical structure; all fasteners are treated with special anti loosening treatment. It has the characteristics of high efficiency and low loss, which can several of power consumption and operation cost, and has significant social benefits. It is a high-tech product promoted by the state.
Primary Voltage Ratings 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2, 24.94, 26.25, 33 or others
Secondary Voltage Ratings 480/277V, 400/230V, 380/220V or customized
H.V. Tap Range ± 2×2.5% HV taps or others
Type Oil immersed distribution transformer
BIL 30/95kV
Standards IEEE, ANSI, IEC, GB
Application Commercial Buildings, Agriculture, Power Distribution Substations etc
Power Rating 400kVA
Certificate ISO, CE, UL
Cooling Method ONAN, ONAN/ONAF, KNAN, KNAN/KNAF
Oil Mineral Oil or FR3
Opeartion Step Down & Step Up
Technical Specifications
Customization Optional
Packing and Shipping
Manufacturer Test
Routine Testing
Application

Technical Specifications

400kVA Oil Immersed Transformer
Technical Specifications
Accessories
  Technical Specifications
Rated Power 400 kVA
Rating Primary Voltage 2.4 - 34.5kV
Secondary Voltage 480/277V
400/230V
380/220V
Customized
Frequency 50/60Hz
Vector Group Dyn11, Yyn0, Dyn5
Winding Material Aluminum/Copper
Efficiency As IEEE, Doe 2016, CAS Std or Customized
Impedance Voltage Nominal 2% or Customized 1.1 - 5.75% 
Altitude ≤1,000m or Customized
Color ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized, etc
Tank material Mild Steel, 304 Stainless Steel
Insulating Oil Weight 525 kg
Total Weight 1830 kg
Outline Dimensions(L×W×H)in. 1850 × 1360 × 1940(mm)
HV Bushing
LV Bushing
Tap changer
Oil level gauge
Oil temperature indicator
Pressure relief device
Pressure vacuum gauge
Lifting hook for complete transformer
Name plate
Radiators
Oil upper filtering valve
Oil drain valve with 3/8" sampler

Customization Optional

400kVA Oil Immersed Transformer
NPC ELECTRIC’s three-phase oil-immersed transformers can be fully customized to meet your specific requirements.
400kVA three-phase oil-immersed transformers have a wide range of optional specifications to fully meet diverse application requirements. In terms of voltage regulation, the tap changer has two options: on-load voltage regulation and off-excitation voltage regulation. On-load voltage regulation can flexibly adjust the voltage according to load changes when the transformer is running without power outages, and is suitable for places with high requirements for voltage stability; off-excitation voltage regulation has a simple structure and low cost, and is suitable for environments with relatively stable voltage.
In addition to conventional oil-immersed self-cooling (ONAN), oil-immersed air cooling (ONAF) can also be used as a cooling method. Oil-immersed air cooling can start the fan to assist in heat dissipation when the transformer load is large, enhance the cooling effect, and ensure that the transformer operates stably under high temperature or high load conditions.

Packing and Shipping

400kVA Oil Immersed Transformer
Our company's 400kVA three-phase oil-immersed transformers follow strict standards during packaging and transportation to ensure that the equipment is fully protected during transportation and arrives safely at the destination. First, after assembly, the transformer will undergo a comprehensive quality inspection and performance test to ensure that it meets factory standards and customer requirements. In order to avoid potential damage during transportation, the exterior and key components of the transformer will be wrapped with waterproof, moisture-proof, and corrosion-resistant materials, especially in the oil tank part, to ensure that the oil seal is tight and prevent leakage. Then, the transformer is placed in a specially designed wooden frame, and the interior of the frame is filled with high-density foam or other shock-proof materials to absorb shock and vibration during transportation and ensure that the transformer is protected from damage during long-distance transportation.
All packaging boxes and shipping containers are marked with clear handling and warning labels to remind porters to handle with caution. In addition, the outer packaging of the transformer will be reinforced to prevent damage caused by external pressure or collision. For different modes of transportation (land, sea, or air), we will choose the appropriate transportation plan according to the actual situation and select professional logistics companies to operate to ensure that the equipment is delivered to the destination on time and safely. During transportation, the logistics company will pay special attention to the loading and unloading of the transformer to ensure safe operation and prevent unnecessary damage to the equipment. Finally, after the transformer arrives at the destination, we will provide detailed unloading, installation, and operation instructions to ensure that the transformer can be put into use quickly and safely.
400kVA Oil Immersed Transformer package
400kVA Oil Immersed Transformer package mini
32
32 years of industry experience

Manufacturer Test

400kVA Oil Immersed Transformer
400kVA Oil Immersed Transformer Progress Test

Progress Test

NPC ELECTRIC manufactures three-phase oil-immersed transformers the strict quality control. The process test of 400kV three-phase oil-immersed transformers mainly includes the following contents:

Production process phase test

Winding interlayer capacitance measurement: During the winding process, the interlayer capacitance of the winding is measured regularly. The change of interlayer capacitance can reflect the winding quality and insulation condition of the winding. By monitoring the interlayer capacitance, possible problems in the winding process, such as insulation damage and winding short circuit, can be discovered in time.

Actual measurement of magnetic field distribution after body assembly: After the body assembly is completed, the magnetic field distribution inside the transformer is actually measured using a magnetic field sensor. Compare the designed magnetic field distribution to check whether there are problems, such as magnetic field distortion, to ensure that the electromagnetic performance of the transformer meets the requirements.

Coating adhesion test after tank painting: After the tank is painted, the adhesion of the coating is tested by the cross-cutting method or the pull-off method. The adhesion of the coating directly affects the anti-corrosion performance of the tank. The test ensures that the coating can be firmly attached to the surface of the tank to prevent the coating from falling off and causing the tank to rust.

30kVA Oil Immersed Transformer  Design Tests

Design Tests

All transformer will be test after finished the production, test items as below:
♦ Insulation Power Factor
♦ Ratio, Polarity, and Phase Relation
♦ Winding Resistance
♦ Impulse Tests
♦ On load Loss Test
♦ No Load Loss Test
♦ Leak Test
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)

China NPC ELECTRIC

Transformer Factory Acceptance Test

The Transformer Factory Acceptance Test (FAT) for 400kVA three-phase oil-immersed transformers is an essential procedure conducted before shipment to ensure the transformer meets all required standards and performs optimally. During the FAT, several critical tests are carried out:

No-load test: Perform a no-load test to confirm whether the current, voltage, loss, and other parameters of the transformer under no load meet the design requirements.

Load test: Test the voltage, current, power loss, etc. of the transformer under rated load and overload conditions to ensure that the transformer operates stably under different working loads.

Short-circuit impedance test: Test the short-circuit impedance of the transformer to ensure that it will not cause excessive pressure on the transformer in the case of a short circuit and meet the design requirements.

Insulation resistance and dielectric strength test: Measure the insulation resistance of components such as windings and casings to check their insulation performance; at the same time, perform a dielectric strength test on the transformer oil to confirm its good insulation ability.

Temperature rise test: Perform a temperature rise test under rated load to ensure that the transformer can continue to operate stably under high load and will not affect performance due to overheating.

Routine Test - Leak Test

Purpose of Testing
The purpose of water leakage test is to check whether there is leakage in the equipment or system, to ensure that it has good sealing and safety during use. The integrity of the equipment can be verified by simulating the pressure or load conditions in the working environment.
Testing Equipment
Leakage current tester (e.g. Fluke, Hioki, Megger, etc.)
Voltage source (usually 500V, 1 KV or 2.5 KV, customized according to test requirements)
Temperature and humidity meter
Ground electrode
Pre-Test Preparation
Ensure that the test environment conditions are suitable for leak testing. Test between 20°C and 30°C. Relative humidity should be less than 75% to avoid moisture affecting the test equipment and results.
Test Progress
Connect the Test Instrument:
Properly connect the test equipment (such as a leak detector) to the pipe, container or sealing structure of the device under test.
Apply Test Voltage:
Apply the appropriate test pressure (e.g. 10 bar, 15 bar, etc.) depending on the equipment's operating pressure or test standard.
Measure and Record
Start the test and record the following parameters:
Applied test pressure
Leakage (can be monitored by flow meter or other equipment)
Time record (to ensure that the test time meets the standard requirements)
Initial pressure and final pressure (if any changes)
Check for leaks
Check for leaks on equipment surfaces and joints by using a foam detector, gas leak detector, or other suitable method.
Repeat Testing (if necessary)
If the test finds leakage or there is any doubt, repeat the test as necessary to verify the sealing of different locations or different equipment parts.
Evaluation Criteria (Reference)
No leakage (excellent): No leakage during the test, the equipment is completely sealed.
Minor leakage (good): Very small leakage is allowed, and it is necessary to judge whether it is qualified according to industry standards.
*These comprehensive tests ensure that each transformer meets performance standards and operates reliably under various conditions.
30kVA Oil Immersed Transformer Routine Test

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Transformers Packaging (1)
Transformers Packaging (1)
Transformers Packaging (2)
Transformers Packaging (2)
Transformers Packaging (3)
Transformers Packaging (3)
Transformers Packaging (4)
Transformers Packaging (4)
Transformers Packaging (5)
Transformers Packaging (5)
Transformers Packaging (6)
Transformers Packaging (6)
Transformers Packaging (7)
Transformers Packaging (7)
Transformers Packaging (8)
Transformers Packaging (8)

Related Products

FAQ From Customers

What is a Transformer?
A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
What are the main uses of a transformer?
The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
Do you have UL listed?
Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.

Welcome your inquiry

Honesty, Integrity, Frugality, Activeness and Passion